High output gas condensing systems

Power HT-A

Single or cascade centralized heating systems installations

Commercial
Floor standing

The range of Power HT-A consists of floor-standing commercial condensing boilers, with output between 121 and 651 kW (50/30°C).


Power HT-A are heating only boilers for centralized systems with the possibility to be connected to a domestic hot water tank.


Cascade option for greater heating demand.

Characteristics


  • Models: 1.115, 1.135, 1.180, 1.230, 1.280, 1.320, 1.430, 1.500, 1.650
  • Modulation up to 1:6 (1:5 for 430-650 kW) reduces on-off cycles for improved efficiency and energy savings
  • High efficiency Aluminium-Silicon exchanger with optimised flows
  • Over-sized water circuit: minimises pressure drops and scale obstructions
  • Glass wool insulation
  • Premix air-gas unit ensures that the burner constantly has an optimal air/gas ratio, for better efficiency and lower energy consumpion
  • Large backlit display
  • Built-in climatic regulation with outdoor sensor included

Technical Specification 

MODELS1.1351.1801.2301.2801.3201.4301.5001.650
Heat input/output
Maximum heat input (heating)kW125170215260300402469610
Minimum heat outputkW20283542488295122
Rated heat output (80/60°C) PratedkW122166210254,5294,3393,8459595,7
Minimum heat output (80/60°C)kW19,226,833,540,247,180,493119,2
Maximum heat output (50/30°C)kW133,1181,3229,6278,1322,1426496,6644,8
Minimum heat output (50/30°C)kW21,329,851,26263,288,9102,8131,5
Useful heat output at 30% of rated heat output and low temperature regime** P1kW40,855,569,784,497,3130,5--
Useful efficiency at rated heat output and high temperature regime* ŋ4%87,787,98888,288,388,3--
Useful efficiency at 30% of rated heat output and low temperature regime** ŋ1%989897,497,597,497,5--
Heating circuit
Maximum pressure heating circuitbar66666666
Maximum inlet temperature heating circuit°C9090909090909090
Temperature range for heating circuit°C25-8025-8025-8025-8025-8025-8025-8025-80
Water contentl29343845537284106
Combustion
Diameter of separate discharge pipesmm160160200200200250250250
Nitrogen oxide emissions NOxmg/kWh383839393936<56<56
Flue gas mass flow rate (max)kg/s0,0570,0770,0970,1180,1360,1890,220,286
Flue gas mass flow rate (min)kg/s0,0090,0130,0160,0190,0220,0390,0460,059
Maximum flue temperature°C6161606160646164
Electrical characteristics
Auxiliary electrical power consumption - Full load elmaxW170200330350410463583750
Auxiliary electrical power - Partial load elminW313440464660--
Auxiliary electrical power - Stand-by PSBW444444--
Power supply voltageV230230230230230230230230
Power supply frequencyHz5050505050505050
Dimensions
Sound power level, indoor LWAdB666767676768--
Net weightkg205340285314344540598674
Dimensions (height/width/depth)mm1455x692x10081455x692x10081455x692x11711455x692x12641455x692x13571526x762x18821526x762x21921526x762x2192

(**) Low temperature: return temperature (at boiler inlet) for condensing boilers 30°C, for low temperature boilers 37°C and for other heaters 50°C.
(*) High temperature setting means 60 °C return temperature at boiler inlet and 80 °C flow temperature at boiler outlet.

Download Area

Leaflet

Get more details and information about Baxi products

Related Products

Luna-Duo-Tec-MP-1

Luna Duo-Tec MP+

Single or cascade centralized heating systems installations
power-ht

Power HT+

Single or cascade centralized heating systems installations
gmc

GMC+

Cabinets for Luna Duo-tec MP+ - single or cascade preassembled installation
Banner-becomedealer_2400x1440

Become a partner

We believe we are stronger together:

Join Baxi in delivering innovative heating and cooling systems.

Get in touch with our International team and discover all the opportunities